Conduit Fill Calculator: NEC Chapter 9 Fill for EMT, PVC and RMC

Add every wire in the run, in any mix of sizes and THHN/THWN-2 or XHHW insulation. See the fill for every trade size at once, the smallest conduit that passes, and how many wires of one size fit.

Conduit Fill Calculator

  1. Wires 1
    0.0133 sq in each0.0399 sq in
  2. Wires 2
    0.0133 sq in each0.0133 sq in
Count the equipment ground if it’s insulated.
1/2 in EMT4 conductors · 0.0532 sq in · 40% fill allowed for 3+ wires
10.0%3/4 in is within the limit (40.0%)
16max 12 AWG THHN / THWN-2 in 3/4 in
Trade sizeInternal areaAllowed areaYour fillResult
1/2 in0.304 sq in0.122 sq in17.5%✓ Fits
3/4 in0.533 sq in0.213 sq in10.0%✓ Fits
1 in0.864 sq in0.346 sq in6.2%✓ Fits
1-1/4 in1.496 sq in0.598 sq in3.6%✓ Fits
1-1/2 in2.036 sq in0.814 sq in2.6%✓ Fits
2 in3.356 sq in1.342 sq in1.6%✓ Fits
2-1/2 in5.858 sq in2.343 sq in0.9%✓ Fits
3 in8.846 sq in3.538 sq in0.6%✓ Fits
3-1/2 in11.545 sq in4.618 sq in0.5%✓ Fits
4 in14.753 sq in5.901 sq in0.4%✓ Fits

Based on NEC Chapter 9 Tables 1, 4 and 5 (wire areas for THHN/THWN-2 and XHHW/XHHW-2). The one-size count applies Chapter 9 Note 7 (round up from 0.8). Fill is only one check: also apply ampacity adjustment for more than 3 current-carrying conductors, and follow the code edition your jurisdiction adopted.

How Do You Calculate Conduit Fill?

Add the area of every conductor from NEC Chapter 9 Table 5, including insulated grounds, and divide by the conduit’s internal area from Table 4. Three or more wires may fill 40%, two wires 31% and one wire 53%. For example, 3/4-inch EMT holds up to sixteen 12 AWG THHN conductors.

Checked against the sources below · How we build and test our calculators

EMT Conduit Fill Chart: Maximum THHN/THWN-2 Wires

Most conductors of one size allowed in EMT, from NEC Chapter 9 Tables 1, 4 and 5 (Note 7 applied).

EMT size14 AWG12 AWG10 AWG8 AWG6 AWG4 AWG2 AWG1/0 AWG
1/2 in129531110
3/4 in22161064211
1 in35261697431
1-1/4 in6145281612753
1-1/2 in84613822161074
2 in13810163362616117

PVC Schedule 40 Conduit Fill Chart

PVC 40 size14 AWG12 AWG10 AWG8 AWG6 AWG4 AWG2 AWG1/0 AWG
1/2 in118531110
3/4 in2115954111
1 in34251596431
1-1/4 in6043271611753
1-1/2 in8259372115974
2 in1359962362616117

Conduit Internal Area by Trade Size (NEC Table 4)

Trade sizeEMT (electrical metallic tubing)PVC Schedule 40PVC Schedule 80Rigid metal conduit (RMC)
1/2 in0.304 sq in0.285 sq in0.217 sq in0.314 sq in
3/4 in0.533 sq in0.508 sq in0.409 sq in0.549 sq in
1 in0.864 sq in0.832 sq in0.688 sq in0.887 sq in
1-1/4 in1.496 sq in1.453 sq in1.237 sq in1.526 sq in
1-1/2 in2.036 sq in1.986 sq in1.711 sq in2.071 sq in
2 in3.356 sq in3.291 sq in2.874 sq in3.408 sq in
2-1/2 in5.858 sq in4.695 sq in4.119 sq in4.866 sq in
3 in8.846 sq in7.268 sq in6.442 sq in7.499 sq in
3-1/2 in11.545 sq in9.737 sq in8.688 sq in10.010 sq in
4 in14.753 sq in12.554 sq in11.258 sq in12.882 sq in

Total internal area; multiply by 0.40 for 3 or more conductors. Always confirm with the NEC edition your jurisdiction has adopted.

Add This Calculator to Your Website, Free

Electrical contractors and supply houses: put the calculator on your site, in your colors, with a button to request your quote.

Preview it

Paste it into any page of your website as an “HTML” or “embed” block. It’s free, needs no account and collects no visitor data.

Questions

How do I calculate conduit fill?

Add up the cross-sectional area of every conductor from NEC Chapter 9, Table 5 (including insulated grounds), then compare it with the conduit’s internal area from Table 4. With three or more conductors, the total may not exceed 40% of the conduit area; one conductor may fill 53% and two conductors 31%.

How many 12 AWG THHN wires fit in 3/4 inch EMT?

Sixteen. The 40% fill area of 3/4-in EMT is 0.213 sq in, and each 12 AWG THHN is 0.0133 sq in. Remember that more than three current-carrying conductors also reduces their ampacity.

Why is the fill limit 40%?

Leaving room in the raceway lets you pull the wires without damaging the insulation and lets heat escape. The 53% and 31% limits for one and two conductors come from Chapter 9, Table 1.

Do grounding wires count toward conduit fill?

Yes. Equipment grounding and bonding conductors count toward fill. Use their actual insulation type, or Chapter 9 Table 8 for bare conductors.

What is the 60% rule for nipples?

A conduit nipple 24 inches or shorter between boxes or enclosures may be filled to 60% of its area (Chapter 9, Note 4), and ampacity adjustment for bundling does not apply to it.

What does Note 7 mean?

When all the conductors are the same size, Chapter 9 Note 7 lets you round up to the next whole conductor if the calculation ends in 0.8 or more. Our one-size count applies it.